e2eb/h or e1eb/h heaters

Posted by john on February 21st, 2003 08:29 PM
In reply to intertherm by Jerome Williams on December 27th, 2002 11:08 PM [Go to top of thread]

Your a/c coil has leaked water into the left front side of the heater
beside the blower where the wires go into the control box, causing the
SEQUENCER to short out internally. This will make the blower run all the
time. Try this... turn off the breakers at the main panel, then unplug
the in-line plug with the orange,grey,black,blue,yellow and red wires.
Now turn the main power back on and see if you see orange light coming
from under the blower, the sequencer IS burnt out and will cause you high
electric bills because one,two or more elements are coming on all the time
and come summer thats around 23 to 100 amps with a/c on... anyhow, good luck john m